Viessmann · Boiler troubleshooting
Adjust the heating curve for a heating circuit
What is going on
Set slope and shift so the supply temperature follows the outside temperature for the system type. Factory slope is 1.4 and shift is 0. Underfloor systems are about slope 0.2 to 0.8, low temperature systems about 0.8 to 1.6, and systems above 167°F (75°C) boiler water are above 1.6.
Check in this order
- Tap the menu button and select Heating.
- Select the required heating circuit.
- Select Heating curve.
- Set Slope and Shift with the +/- keys.
- Confirm the entry.
Applies to: Vitocrossal 200 CI2 heating circuits
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 17-18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.