Viessmann · Boiler troubleshooting
Check fixed high limit
What is going on
Check the fixed high limit if the burner control cannot be reset after a fault shutdown, although the boiler water temperature is below approx. 167°F (75°C).
Likely causes
- Fixed high limit open or defective after a fault shutdown
Check in this order
- Disconnect main power before opening the boiler.
- Remove the cables from the fixed high limit.
- Check continuity of the fixed high limit with a multimeter.
- Remove and replace a defective fixed high limit.
- After startup, press reset button R on the boiler control.
Applies to: Fixed high limit on Vitodens 200-W B2HA
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 19, 28, 35 Service Instructions, p. 81. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.