Viessmann · Boiler troubleshooting

Combustion air device adaptor wiring (CM2)

Vitotronic 100

What is going on

Connecting the combustion air blower on the CM2 control, which uses the TR terminals.

Check in this order

  1. Disconnect power to the control and burners.
  2. Mount the combustion air device adaptor (part 7134 563) on the DIN rail inside the boiler junction box, following the adaptor manual.
  3. Remove plug 150 from the Vitotronic control. Remove the jumper between the two TR terminals.
  4. Using 14 AWG field wire, connect neutral to terminal 16, TR left to terminal 18, and TR right to terminal 19 on the DIN rail.
  5. Reinstall plug 150 and the DIN rail connections as shown.
  6. Connect BK2 to terminal 18 and BK3 to terminal 19. Do not reverse them.
  7. Wire the blower (120 VAC, max 5 FLA, AWG 14) to the adaptor. The proving switch must be normally open and rated 120 VAC.
  8. Provide disconnect and overcurrent protection as required by local codes.

Applies to: Vitocrossal 300 CM2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 installation manual, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.