Expansion tank sizing and placement
What is going on
Size the expansion tank for the total boiler and system water volume and temperature. An undersized tank lets system water blow out the relief valve and draws in make-up water, which can eventually fail the boiler. Boiler water content is listed on page 120.
Check in this order
- Check the expansion tank size against the boiler and system water volume and temperature.
- Place the tank as shown in the manual or by a recognized design method, following the tank maker's instructions.
- Connect the tank to the air separator only if the separator is on the pump suction side.
- Install the system fill connection at the same point as the expansion tank connection to the system.
Applies to: SVF 1500-3000 Series 1
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.