Weil-McLain · Boiler troubleshooting

Check flame signal

Ultra Series 4

What is going on

Read the flame signal in Diagnostics/Inputs. It must be at least 20 above the shutdown value for the model (Figure 119).

Likely causes

  • Fouled ignitor
  • Damaged ignitor insulation
  • Poor ground path to the ignitor
  • Vent/air piping or heat exchanger problem if the signal stays low

Check in this order

  1. Go to Diagnostics/Inputs on the U-Control display (see Figure 115, page 102).
  2. Confirm the flame signal is at least 20 above the Figure 119 shutdown value.
  3. If the signal falls below that, the U-Control raises the firing rate to recover it.
  4. If the signal is low, clean the ignitor. If it does not improve and the ground wiring and continuity are good, replace the ignitor.
  5. If the signal is still low, inspect the vent and air piping, then the heat exchanger, and clean it if needed.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 112-113. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.