Weil-McLain · Boiler troubleshooting
Check flame signal
What is going on
Read the flame signal in Diagnostics/Inputs. It must be at least 20 above the shutdown value for the model (Figure 119).
Likely causes
- Fouled ignitor
- Damaged ignitor insulation
- Poor ground path to the ignitor
- Vent/air piping or heat exchanger problem if the signal stays low
Check in this order
- Go to Diagnostics/Inputs on the U-Control display (see Figure 115, page 102).
- Confirm the flame signal is at least 20 above the Figure 119 shutdown value.
- If the signal falls below that, the U-Control raises the firing rate to recover it.
- If the signal is low, clean the ignitor. If it does not improve and the ground wiring and continuity are good, replace the ignitor.
- If the signal is still low, inspect the vent and air piping, then the heat exchanger, and clean it if needed.
Applies to: Ultra 80, 105, 155, 230, 299, 399
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 gas-fired water boiler manual, p. 112-113. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.