Weil-McLain · Boiler troubleshooting
Check pressure switch sense hoses
What is going on
Sense lines must be in good condition and on the correct fittings. Wrong or loose lines cause unreliable operation.
Likely causes
- Hoses swapped or disconnected.
- Cracked or worn plastic reference line.
Check in this order
- Check every pressure switch sense hose against Figure 78.
- The blue hose runs from the gas valve to the shroud.
- The black hose runs from the flue pressure switch to the hose barb on the condensate dish.
- Check the plastic gas valve/venturi reference line is attached and in good shape.
- Replace any hose or line that is damaged or misrouted.
Applies to: Pressure switch sense lines
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.