Zoning with zone valves, two zones (no DHW)
What is going on
Two space heating zones with zone valves. INPUT 1 is reserved for the system circulator, so it cannot be used for a wired thermostat. The system must have a bypass pressure regulating valve because flow can occur with all zone valves closed.
Check in this order
- Wire thermostats to INPUT 2 and INPUT 3 and keep both on PRIORITY 2.
- Assign INPUT 1 to AUX PUMP/OUTPUT.
- Select ANY INPUT BY ITS PRIORITY as the activation condition so the system pump runs on any zone call.
- Confirm PRIORITY 2 RUN AUX PUMP/OUT is set to YES.
- Install a bypass pressure regulating valve in the system.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.