Zoning with zone valves, two zones (no DHW)

SlimFit Series 2

What is going on

Two space heating zones with zone valves. INPUT 1 is reserved for the system circulator, so it cannot be used for a wired thermostat. The system must have a bypass pressure regulating valve because flow can occur with all zone valves closed.

Check in this order

  1. Wire thermostats to INPUT 2 and INPUT 3 and keep both on PRIORITY 2.
  2. Assign INPUT 1 to AUX PUMP/OUTPUT.
  3. Select ANY INPUT BY ITS PRIORITY as the activation condition so the system pump runs on any zone call.
  4. Confirm PRIORITY 2 RUN AUX PUMP/OUT is set to YES.
  5. Install a bypass pressure regulating valve in the system.

Applies to: SF1000L/R, SF1500L/R, SF2000L/R

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.