Steam gauge glass cleaning and replacement
What is going on
Keep the gauge glass clean so the waterline can be read. Normal waterline is halfway up the gauge glass.
Likely causes
- Sediment or deposits in the gauge glass
- Broken gauge glass
Check in this order
- Make sure boiler pressure is low to avoid severe burns.
- Close the lower gauge cock.
- Open the pet cock.
- Open the lower gauge cock and let a small amount of water flush out through the pet cock.
- Close the pet cock.
- If the gauge glass breaks, close both gauge cocks and replace the glass. Do not use thin glass tubing.
Applies to: EG and PEG steam boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.