Check control module fuses

Ultra Series 4

What is going on

Check both fuses before replacing the control module or major components such as the blower.

Likely causes

  • Blown low voltage fuse
  • Blown line voltage fuse

Check in this order

  1. Turn off power to the boiler at the external line switch.
  2. Remove the jacket door and top panel. Swing the control panel forward to reach the U-Control module.
  3. Remove and inspect both fuses.
  4. Replace the low voltage fuse with a 3 A fast-blow (Littelfuse 257003) if needed.
  5. Replace the line voltage fuse with a 12 A slow-blow (Littelfuse 326012P) if needed.
  6. Never jumper a fuse or fit a different rating.
  7. Refit the top panel and jacket door, restore power, and verify operation.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 116. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.