Viessmann · Boiler troubleshooting
Fixed high limit test (RTD sensors)
What is going on
Test the fixed 210°F (99°C) high limit by forcing a call for heat and throttling water flow. The burner should lock out at the limit. Viessmann is not responsible for overheating damage during this test.
Check in this order
- Jumper terminals 2-3 of plug 146 on the GW6B control to simulate a call for heat. On GW6B cascade systems, use the emissions test switch instead (top left, ladder sign).
- Set coding address 9B (external heat demand) to a maximum of 241°F (116°C), higher than the fixed high limit. Skip this if using the emissions test switch.
- Set item #4 'Max. boiler water temperature' under menu 6 of the burner control (GC310) to 243°F (117°C), higher than the fixed high limit. Factory default is 203°F (95°C).
- Start the burner with the call for heat.
- Slowly throttle the water flow to the boiler.
- Watch the temperature on the GW6B control.
- When the fixed high limit is reached, the burner locks out with F F2 displayed. The fan runs for 10 minutes.
- Reset the fault manually only after boiler water temperature drops.
- Restore item #4 under submenu 6 and coding address 9B to original settings.
Applies to: Vitocrossal 200 CM2 with GW6B control and GC310 burner control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.