Inspect ignition electrode and ignition wiring
What is going on
Clean or replace the electrode and check the ignition cable and ground wiring.
Check in this order
- Remove the ignition electrode from the heat exchanger.
- Remove white oxides with steel wool. If it cannot be cleaned well, replace the ignitor.
- Reinstall the electrode. Make sure the gasket is in good condition and correctly positioned. Replace the gasket if needed.
- Confirm the ignition electrode ground wire is under the top screw that holds the ignitor to the casting.
- Check ignition cable resistance. A good cable reads 900 to 1000 ohms. Replace the cable if the reading is not acceptable.
- Inspect the ground wire from the electrode to the ground terminal strip.
- Check that all wiring is in good condition and securely attached.
- Check ground continuity with a continuity meter. Replace ground wires if the results are not satisfactory.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 93. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.