Weil-McLain · Boiler troubleshooting

Inspect ignition electrode and ignition wiring

SlimFit Series 3

What is going on

Clean or replace the electrode and check the ignition cable and ground wiring.

Check in this order

  1. Remove the ignition electrode from the heat exchanger.
  2. Remove white oxides with steel wool. If it cannot be cleaned well, replace the ignitor.
  3. Reinstall the electrode. Make sure the gasket is in good condition and correctly positioned. Replace the gasket if needed.
  4. Confirm the ignition electrode ground wire is under the top screw that holds the ignitor to the casting.
  5. Check ignition cable resistance. A good cable reads 900 to 1000 ohms. Replace the cable if the reading is not acceptable.
  6. Inspect the ground wire from the electrode to the ground terminal strip.
  7. Check that all wiring is in good condition and securely attached.
  8. Check ground continuity with a continuity meter. Replace ground wires if the results are not satisfactory.

Applies to: SlimFit 550 and 750 Series 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 93. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.