Initial start-up checklist
What is going on
Complete these checks before starting the system.
Check in this order
- Confirm the boiler room fresh air intake is open.
- Confirm the chimney and all flue pipes are connected, sealed and unobstructed inside.
- Confirm the expansion tank is correctly sized and working.
- If the tank precharge is below system static pressure, raise the membrane pressure slightly above system pressure.
- Fill the system with water and bleed all air. Confirm the system is fully vented.
- Install the automatic fill valve per its instructions and follow local backflow preventer rules.
- Pressure test the boiler and piping at no more than 1½ times the maximum operating pressure. Remove the pressure relief valve during the test.
- Correct all leaks.
- Confirm the fuel supply is adequate and open the oil shut-off valve.
Applies to: Vitorond 100 VR1 22 to 33, 91 to 140
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100, VR1 Installation and Service Instructions, p. 36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.