Weil-McLain · Boiler troubleshooting
Thermostat and dry contact heat demand wiring
What is going on
Inputs 1 to 3 take dry contact calls for heat. They do not supply 24 V.
Check in this order
- Wire thermostats, aquastats or end switches as dry contacts on Input 1, 2 or 3.
- If a thermostat needs continuous 24 V, connect its common wire to P11 pin 2 and keep total current per thermostat within its limit.
- For 3-wire zone valves, use relays to make dry contacts for the control inputs.
- Do not put 24 V from the boiler into any thermostat circuit.
Applies to: SlimFit 550/750 Series 3 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.