Thermostat and dry contact heat demand wiring

SlimFit Series 3

What is going on

Inputs 1 to 3 take dry contact calls for heat. They do not supply 24 V.

Check in this order

  1. Wire thermostats, aquastats or end switches as dry contacts on Input 1, 2 or 3.
  2. If a thermostat needs continuous 24 V, connect its common wire to P11 pin 2 and keep total current per thermostat within its limit.
  3. For 3-wire zone valves, use relays to make dry contacts for the control inputs.
  4. Do not put 24 V from the boiler into any thermostat circuit.

Applies to: SlimFit 550/750 Series 3 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.