Viessmann · Boiler troubleshooting

Reading the brief scan

Vitocrossal 300

What is going on

The brief scan shows 9 lines with 6 fields each: software versions, system type, KM BUS participants, mixing valve and remote control types, pump types, and calibration details. A sensor that is faulty shows - - - in place of its reading.

Check in this order

  1. Press OK and the second button together for about 4 sec.
  2. Select Diagnosis, then Brief scan, then press OK.
  3. Read line by line against the field tables on the page.
  4. If a value shows - - -, check that sensor first.

Applies to: Boiler control unit diagnosis

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.