Viessmann · Boiler troubleshooting
Check the fixed high limit (TÜV TEST)
What is going on
Test the boiler's fixed high limit cut-out by bridging the adjustable high limit while the boiler heats up.
Check in this order
- Make sure a minimum supply is running. Recirculated water should be at least 10% of the flow at rated load.
- Reduce the heat consumption as far as possible.
- Press and hold the TÜV TEST button for the whole check. The adjustable high limit is bridged.
- Let the burner run until the boiler water reaches the safety temperature and the fixed high limit trips.
- Release the TÜV TEST button and let the boiler water drop 15 to 20°C (27 to 36°F) below the selected safety temperature.
- Reset the fixed high limit with the E button.
Applies to: Vitotronic 300 GW2 on Viessmann boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 64-65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.