Viessmann · Boiler troubleshooting

Check the fixed high limit (TÜV TEST)

Vitotronic 300

What is going on

Test the boiler's fixed high limit cut-out by bridging the adjustable high limit while the boiler heats up.

Check in this order

  1. Make sure a minimum supply is running. Recirculated water should be at least 10% of the flow at rated load.
  2. Reduce the heat consumption as far as possible.
  3. Press and hold the TÜV TEST button for the whole check. The adjustable high limit is bridged.
  4. Let the burner run until the boiler water reaches the safety temperature and the fixed high limit trips.
  5. Release the TÜV TEST button and let the boiler water drop 15 to 20°C (27 to 36°F) below the selected safety temperature.
  6. Reset the fixed high limit with the E button.

Applies to: Vitotronic 300 GW2 on Viessmann boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 64-65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.