Navien · Boiler troubleshooting
Wiring a zone valve system
What is going on
Zone valves are powered from the boiler's 24 VAC supply, which is limited by the 75 VA transformer.
Check in this order
- Connect each zone valve to the boiler through its COM and NO or NC terminal, as set by the valve type.
- NO (normally open) valve power is on while the valve is operating and turns off when it stops.
- NC (normally closed) valve power is on while the valve is stopped and turns off when it operates.
- Connect the system pump to the Zone Pump 3 terminals. The system pump must be on those terminals in zone valve systems.
- Keep the total zone valve draw at or below 72 VA. If it is higher, add an external zone valve controller.
- For Taco 570/571 and Taco Sentry valves, connect zone valve 1 to boiler COM and zone valve 2 to boiler NO.
- For thermostats with their own 24 VAC power, wire each thermostat input with its 24 VAC neutral and line.
Applies to: NCB700 zone valve systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 44, 45, 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.