Wiring a zone valve system

NCB700

What is going on

Zone valves are powered from the boiler's 24 VAC supply, which is limited by the 75 VA transformer.

Check in this order

  1. Connect each zone valve to the boiler through its COM and NO or NC terminal, as set by the valve type.
  2. NO (normally open) valve power is on while the valve is operating and turns off when it stops.
  3. NC (normally closed) valve power is on while the valve is stopped and turns off when it operates.
  4. Connect the system pump to the Zone Pump 3 terminals. The system pump must be on those terminals in zone valve systems.
  5. Keep the total zone valve draw at or below 72 VA. If it is higher, add an external zone valve controller.
  6. For Taco 570/571 and Taco Sentry valves, connect zone valve 1 to boiler COM and zone valve 2 to boiler NO.
  7. For thermostats with their own 24 VAC power, wire each thermostat input with its 24 VAC neutral and line.

Applies to: NCB700 zone valve systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 44, 45, 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.