Viessmann · Boiler troubleshooting
Pressure relief valve installation
What is going on
Install the factory-supplied approved pressure relief valve on the boiler water supply connection. Do not put an isolation valve between the boiler and the relief valve. Pipe the discharge close to a floor drain, never outdoors.
Check in this order
- Install the pressure relief valve on the boiler water supply connection.
- Install the discharge pipe, minimum 3/4 in, unthreaded at the end.
- End the discharge pipe about 6 in (150 mm) above a floor drain.
- Orient the discharge pipe so it cannot scald people.
- Do not install any isolation valve between the boiler and the relief valve.
- Check that the expansion tank piping is at least 3/4 in.
Applies to: Vitorond 100 VR1 40 to 63, 161 to 245
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service instructions, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.