Weil-McLain · Boiler troubleshooting
Installing the relief valve and discharge piping
What is going on
The relief valve is shipped loose and goes in the 1-1/4 inch coupling (SVF 1500/2000) or 2 inch coupling (SVF 2500/3000) on top of the supply outlet pipe. The discharge must run to a safe location that will not freeze. Discharge line must be as short as possible, the same size as the valve outlet, pitched down from the valve, end plain (not threaded) at a material rated for 375 °F or higher, and end at least 6 inches above a floor drain where discharge is visible. No shutoff valve may be placed between the relief valve and boiler or in the discharge line, and nothing may obstruct the line. After filling and pressurizing, lift the lever to test that the valve discharges freely; replace the valve if it fails.
Check in this order
- Install the relief valve in the 1-1/4 inch (SVF 1500/2000) or 2 inch (SVF 2500/3000) coupling on top of the supply pipe.
- Pipe the discharge downward, short and full size, ending plain at least 6 inches above a visible floor drain.
- Confirm no shutoff valve or obstruction exists in the discharge line or between the valve and boiler.
- After filling and pressurizing, lift the lever and confirm free discharge; replace the valve if it does not operate.
Applies to: All SVF 1500-3000 models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.