Expansion tank and water connections

SlimFit Series 3

What is going on

General piping rules that apply to every layout on pages 16 to 19.

Check in this order

  1. Provide a system expansion tank following the guidelines on p. 14.
  2. Do not use a closed-type expansion tank when connected to a water heater with an automatic vent.
  3. Install a union on the boiler supply and return as close to the boiler as possible.
  4. Place the boiler drain valve at 3/4 inch or larger.
  5. Strap system supply and return sensors to the lines at least 6 pipe diameters (max 3 ft) from the boiler connection tees.
  6. Install a P/T gauge on the boiler outlet.

Applies to: SF-550 and SF-750

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual 550-100-559/0725, pp. 16-19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.