Weil-McLain · Boiler troubleshooting
Expansion tank and water connections
What is going on
General piping rules that apply to every layout on pages 16 to 19.
Check in this order
- Provide a system expansion tank following the guidelines on p. 14.
- Do not use a closed-type expansion tank when connected to a water heater with an automatic vent.
- Install a union on the boiler supply and return as close to the boiler as possible.
- Place the boiler drain valve at 3/4 inch or larger.
- Strap system supply and return sensors to the lines at least 6 pipe diameters (max 3 ft) from the boiler connection tees.
- Install a P/T gauge on the boiler outlet.
Applies to: SF-550 and SF-750
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual 550-100-559/0725, pp. 16-19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.