Setting the boiler on its legs and leveling

SVF

What is going on

Casters are only for moving the boiler into place. Front and piping-end casters swivel, middle casters are fixed. The boiler must be carried on the leveling legs, with the base at least 1-1/2 inches above the floor and wheels off the ground. Level front to back and side to side on the cover plate. For seismic or bolted installs, use the seven mounting brackets (28 holes, 3/8 inch bolts or anchors) and keep the same 1-1/2 inch minimum. Remove jacket panels to reach the leg bolts and jam nuts.

Check in this order

  1. Roll the boiler into position and set the leg adjusters down until they touch the floor.
  2. Remove jacket panels as needed to reach bolt heads and jam nuts.
  3. Extend the legs until the base is at least 1-1/2 inches above the floor.
  4. Level the boiler front to back and side to side, measuring on the cover plate.
  5. For seismic work, bolt the seven brackets with 3/8 inch bolts or anchors, keeping the 1-1/2 inch minimum.

Applies to: All SVF 1500-3000 models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.