Select a circulator for a direct-connected DHW water heater

Ultra Series 4

What is going on

Size the DHW loop circulator for a water heater piped across the Ultra boiler, using the boiler head loss and piping head loss tables.

Check in this order

  1. Pipe the DHW tank and boiler per the suggested diagrams.
  2. From the water heater data, note the required boiler flow in GPM at 190°F.
  3. From the same data, note the water heater pressure drop in feet w.c. (this is H3).
  4. In the pipe sizing table, find the boiler model and select the flow rate just above the required flow.
  5. Read H1 (boiler head loss) and H2 (piping head loss) from that row, using the listed copper pipe size.
  6. Add H1 + H2 + H3 to get total head loss.
  7. Select a circulator that delivers the required GPM at that total head loss, using the pump curves.

Applies to: Ultra boilers on combined space heating/DHW systems with a direct-connected water heater

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.