Select a circulator for a direct-connected DHW water heater
What is going on
Size the DHW loop circulator for a water heater piped across the Ultra boiler, using the boiler head loss and piping head loss tables.
Check in this order
- Pipe the DHW tank and boiler per the suggested diagrams.
- From the water heater data, note the required boiler flow in GPM at 190°F.
- From the same data, note the water heater pressure drop in feet w.c. (this is H3).
- In the pipe sizing table, find the boiler model and select the flow rate just above the required flow.
- Read H1 (boiler head loss) and H2 (piping head loss) from that row, using the listed copper pipe size.
- Add H1 + H2 + H3 to get total head loss.
- Select a circulator that delivers the required GPM at that total head loss, using the pump curves.
Applies to: Ultra boilers on combined space heating/DHW systems with a direct-connected water heater
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.