Install system supply and return temperature sensors
What is going on
Recommended for primary/secondary piping. Required for proper control.
Check in this order
- Use two strap-on sensors (separate kit). For pipe larger than 5 in. or non-metallic pipe, use immersion sensors.
- Attach one sensor to the system supply piping and one to the system return piping.
- Locate the supply sensor at least six pipe diameters, but no more than 3 ft, downstream from the boiler connection.
- Wire the return sensor to J19 pins 1 and 2.
- Wire the supply sensor to J19 pins 3 and 4.
- Thermostat wire can be used for the sensor leads.
Applies to: ECO Tec Series 3 primary/secondary systems
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.