Heating circuit control, quick heat-up and quick setback

Vitocrossal 300 CA3B

What is going on

Heating circuits with mixing valve adjust supply temperature. Quick heat-up and setback apply when room temperature must change by at least 4°F (2 K).

Check in this order

  1. Quick heat-up raise set room temperature by 4°F (2 K) or more by enabling comfort mode, switching from reduced to standard, or using start optimization (coding b7). Stops when set room temperature is reached.
  2. Quick setback lower set room temperature by 4°F (2 K) or more by activating economy mode, switching from standard to reduced, or using shutdown optimization (coding c1). Ends when set room temperature is reached.
  3. Room temperature influence is set with coding b0 (hook-up), b2 and b6 in the Heating circuit group.
  4. The control unit uses an average of actual and adjusted outdoor temperature.

Applies to: Heating circuits 1 to 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.