Heating circuit control, quick heat-up and quick setback
What is going on
Heating circuits with mixing valve adjust supply temperature. Quick heat-up and setback apply when room temperature must change by at least 4°F (2 K).
Check in this order
- Quick heat-up raise set room temperature by 4°F (2 K) or more by enabling comfort mode, switching from reduced to standard, or using start optimization (coding b7). Stops when set room temperature is reached.
- Quick setback lower set room temperature by 4°F (2 K) or more by activating economy mode, switching from standard to reduced, or using shutdown optimization (coding c1). Ends when set room temperature is reached.
- Room temperature influence is set with coding b0 (hook-up), b2 and b6 in the Heating circuit group.
- The control unit uses an average of actual and adjusted outdoor temperature.
Applies to: Heating circuits 1 to 3
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.