Viessmann · Boiler troubleshooting
Checking outside temperature sensor
What is going on
Resistance test of the outside temperature sensor. Sensor type NTC 10 kΩ. The resistance curve chart is not legible in this extract.
Likely causes
- Sensor or lead faulty
Check in this order
- Switch OFF power if needed and pull plug X3 from the control unit.
- Test resistance across terminals X3.1 and X3.2 on the disconnected plug and compare with the curve.
- If values deviate severely, disconnect the wires at the sensor and repeat the test on the sensor.
- Replace the lead or the outside temperature sensor depending on the result.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 78. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.