Viessmann · Boiler troubleshooting

External demand via dry contact

Vitotronic 300-KVitotronic 200

What is going on

A closed dry contact runs the burner load-dependent. Supply water is heated to the set value in coding address 9B (General group) on the Vitotronic 300-K, and is limited by the boiler supply temperature maximum set in coding address 06 (Boiler group) on the Vitotronic 200. Connect the contact to plug aVH (no code needed) or to extension EA1 (accessory).

Check in this order

  1. Use a potential-free dry contact. Live contacts cause shorts or phase failure.
  2. Connect to plug aVH (no code needed), or to extension EA1.
  3. If using extension EA1, set coding 5D, 5E or 5F (General group) to 2.
  4. Set coding 9B to the required supply water temperature.

Applies to: External demand contact

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.