Viessmann · Boiler troubleshooting
Check mixing valve motor rotation for extension kit
What is going on
The boiler runs a self-test on power-up that opens and closes the mixing valve. If the flow temperature drops when the valve should open, the motor runs the wrong way or the valve set is fitted incorrectly.
Likely causes
- Motor running in wrong direction
- Mixing valve set incorrectly fitted
Check in this order
- Power up the boiler and let the self-test run.
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, reverse the motor rotation or check the valve set fitting.
- To reverse the rotation remove the upper casing cover of the extension kit, swap the cores at terminals '|' and '~' at plug gS, and refit the casing cover.
Applies to: Vitodens 200-W B2HB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB service instructions, p. 85. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.