Weil-McLain · Boiler troubleshooting
Boiler circulator location and flow limits
What is going on
The boiler circulator must be supplied by the installer, placed only on the return piping. Wrong placement or sizing causes unreliable operation and nuisance shutdowns.
Likely causes
- Circulator on supply piping, which can starve the pump intake
- Flow too low for the heat exchanger
- Flow too high, causing erosion
Check in this order
- Install the circulator only on the boiler return piping, in a location shown in this manual.
- Select a circulator to give adequate boiler flow. A Taco 1400-50 or equivalent works for most applications.
- The control reduces firing when temperature rise passes 45°F and shuts the burner off at 58°F. Check the flow if this happens.
- For a variable speed (modulating) pump, minimum flow is 4 GPM on the SF-550 and 5 GPM on the SF-750. Control the pump to raise flow between minimum and full fire.
Applies to: SF-550 and SF-750 boiler loop
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 550/750 Series 3 boiler manual, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.