Inspect the ignition electrode and wiring

SVF 500/600 Series 1

What is going on

Igniter and flame sense assembly inspection and cleaning. Boiler must be cold and the gas shut off first.

Likely causes

  • White oxide buildup on the ignition electrode
  • Cracked or damaged igniter
  • Worn or damaged ignition cable or ground wire

Check in this order

  1. Shut off power to the boiler
  2. Close the external manual gas valve
  3. Let the boiler cool to room temperature if it has been firing
  4. Disconnect the ground wire and ignition cable from the ignition electrode
  5. Use a 3 mm Allen wrench to remove the two screws holding the electrode to the cover plate, then carefully remove the igniter with flame sense assembly
  6. Discard the ignition electrode gasket
  7. Remove white oxides from the electrode with steel wool; clean the gasket surfaces on the igniter flange and the cover plate mating surface
  8. Replace the igniter if it is cracked or damaged or cannot be cleaned properly
  9. Slide a new gasket onto the electrode and set the assembly aside
  10. Check ignition cable resistance (see the electrical check setting)
  11. Verify all wiring is in good condition and securely attached
  12. Check the ground wire from the heat exchanger access cover to the control tray ground screw (see the electrical check setting); replace the ground wire if results are not satisfactory
  13. Confirm the igniter rods are parallel and set the spark gap as specified (see notes)

Applies to: SVF 500/600 Series 1 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 109. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.