Pilot lights but main valve will not come on (Chart 3)

EG / PEG Series 7

What is going on

Troubleshooting chart for steam boilers where the pilot lights but the main valve does not come on, with or without a vent damper.

Likely causes

  • No 24 VAC between MV and PV on the ignition control
  • Inlet gas pressure outside 5.0 to 14.0 in w.c.
  • Loose main valve wiring
  • Sense wire or sensing probe faulty or shorted
  • Low flame signal

Check in this order

  1. Check for 24 VAC between terminals MV and PV on the ignition control. If absent, replace the ignition control.
  2. Check inlet gas pressure. It should be at least 5.0 in w.c. and not more than 14.0 in w.c. If low or high, contact the gas supplier to correct the pressure.
  3. Check that the main valve wiring is secure at its terminals.
  4. Check whether the spark stays on for more than a few seconds after the pilot is established. If it does, the chart calls for pilot assembly replacement.
  5. Make sure the sense wire is not wrapped around any pipe or accessory, and is securely attached to the sense terminal and pilot assembly.
  6. Check that the sensing probe ceramic is not cracked, and that the sense wire or probe is not shorted to a metal surface.
  7. Check sense wire continuity and the condition of the insulation. Replace the parts if they are faulty.
  8. Measure flame signal detach the sense lead from the ignition control, connect the negative microammeter lead to the sense terminal and the positive lead to the sense wire from the pilot assembly, disconnect the main valve lead from MV, then energize the system.
  9. The pilot should read at least 1.0 microamp for the Honeywell/Resideo S8620C control, or at least 0.1 microamp for the United Technologies 1003-611A control.
  10. If the flame signal is below the minimum, check gas pressure, clean the pilot assembly, tighten mechanical and electrical connections, and check system grounding.

Applies to: EG and PEG steam boilers, with or without vent damper

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.