Indirect DHW aquastat wiring

Evergreen Series 2

What is going on

The DHW aquastat can go on any one input/output pair. That input must be assigned to Priority 1.

Check in this order

  1. Wire the DHW aquastat contact to any one of the four inputs.
  2. Wire the DHW pump or valve to the matching output.
  3. Assign that input to Priority 1 in the Wizard or manually in the System Settings menu.
  4. Check that Priority 1 settings suit the indirect tank, since its defaults are set for direct-piped indirect DHW.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 50. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.