Viessmann · Boiler troubleshooting

Application 4: two heat circuits, ZC1 low-temperature and air handler on HC2

Vitodens 222-F

What is going on

Two circuits at different temperatures. ZC1 is a low-temperature circuit and the air handler is a mid/high-temperature circuit. A thermostatic mixing valve must protect ZC1 from high water temperature when the air handler runs. The air handler controls the P3 circulator in heat circuit 2 and its heat demand must be a dry contact. The radiant circuit dry contact can come from a thermostat, zone valve or multi-zone controller. Hydraulically separate the boiler and system loops with closely spaced tees or a low-loss header.

Check in this order

  1. Wire the outdoor sensor and the low-loss header sensor as shown.
  2. Wire the air handler heat demand as a potential-free dry contact.
  3. Wire the infloor heat control dry contact to the radiant circuit.
  4. Fit a thermostatic mixing valve to protect ZC1 when the air handler is running.
  5. Confirm the P1 boiler circulator is used; it is built into the boiler.

Applies to: Application code VD2T 2HC2T2ZP.01 (Application 4, pages 38-39, 42-44)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 222-F B2TB application guide, p. 38-40, 42-43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.