Install the condensate drain and siphon
What is going on
The boiler has a built-in condensate trap. The field drain must be inspectable and must not be fed by other appliances.
Check in this order
- Remove the condensate siphon from the boiler.
- Fill the siphon with water and reinstall it on the boiler.
- Connect the field drain to the siphon outlet using 3/4 in. diameter discharge tubing (CPVC, PVC or other approved material).
- Install the drain pipe with a suitable downward gradient.
- Terminate the drain into an open or vented drain as close to the boiler as possible to prevent siphoning.
- Ventilate the pipe between the siphon trap and the neutralization unit, if one is used.
- If the boiler condensate outlet is lower than the drain, install a condensate pump approved for condensing boilers, with an overflow switch.
- If the boiler is installed even with the ground, keep the condensate drain no more than 2 in. (50 mm) above ground.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.