Viessmann · Boiler troubleshooting

Install the condensate drain and siphon

Vitocrossal 300 CU3A

What is going on

The boiler has a built-in condensate trap. The field drain must be inspectable and must not be fed by other appliances.

Check in this order

  1. Remove the condensate siphon from the boiler.
  2. Fill the siphon with water and reinstall it on the boiler.
  3. Connect the field drain to the siphon outlet using 3/4 in. diameter discharge tubing (CPVC, PVC or other approved material).
  4. Install the drain pipe with a suitable downward gradient.
  5. Terminate the drain into an open or vented drain as close to the boiler as possible to prevent siphoning.
  6. Ventilate the pipe between the siphon trap and the neutralization unit, if one is used.
  7. If the boiler condensate outlet is lower than the drain, install a condensate pump approved for condensing boilers, with an overflow switch.
  8. If the boiler is installed even with the ground, keep the condensate drain no more than 2 in. (50 mm) above ground.

Applies to: Vitocrossal 300 CU3A 26 to 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.