Weil-McLain · Boiler troubleshooting

Remote modulation setup with 0-10VDC input

Evergreen Series 2

What is going on

A 0-10VDC signal drives boiler modulation. Input 2 must be changed to a 0-10V source after the Wizard is done.

Check in this order

  1. Wire the 0-10VDC positive signal to J16 terminal 6 and the common to terminal 5.
  2. Do not wire anything to Input 2.
  3. After the Wizard is complete, open the System Settings menu, select INPUT 2, and change SOURCE to 0-10v.
  4. Confirm OUTPUT 2 switches on and off with the heat demand.

Applies to: Evergreen 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.