Radiators or baseboard cold or noisy (oil water boiler)
What is going on
Some heat emitters do not heat, or they gurgle.
Likely causes
- Air in the system
- System pressure low
- High limit set too low
Check in this order
- Bleed air from the radiator or baseboard vents. Start on the lowest floor and open each vent until water comes out.
- Check system pressure. Normal residential cold fill is about 12 psig. If pressure is low, look for leaks right away and refill.
- Raise the high limit if it is set too low (max 220 F).
Applies to: WGO-2 to WGO-9 oil-fired water boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7; Start-up p.27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.