Radiators or baseboard cold or noisy (oil water boiler)

Weil-McLain WGO Series 4

What is going on

Some heat emitters do not heat, or they gurgle.

Likely causes

  • Air in the system
  • System pressure low
  • High limit set too low

Check in this order

  1. Bleed air from the radiator or baseboard vents. Start on the lowest floor and open each vent until water comes out.
  2. Check system pressure. Normal residential cold fill is about 12 psig. If pressure is low, look for leaks right away and refill.
  3. Raise the high limit if it is set too low (max 220 F).

Applies to: WGO-2 to WGO-9 oil-fired water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WGO Series 4 Water Boiler Manual 550-142-331/0225, Troubleshooting p.7; Start-up p.27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.