Weil-McLain · Boiler troubleshooting

No outdoor sensor installed

Weil-McLain ECO Tec Series 3

What is going on

The outdoor sensor ships with the boiler and is required unless the job meets one of the exemptions. Without it, two settings must be changed.

Likely causes

  • Sensor not installed on an exempt job
  • Sensor left off on a job that is not exempt

Check in this order

  1. Exemptions an energy management system lowers boiler water temperature as load drops, the boiler does no space heating, or it is part of a multi-boiler system of 300,000 BTU/h total or more.
  2. Without the sensor, set Target Adjust in each priority to NONE (fixed supply temperature) or 0-10V (remote target).
  3. Set WWSD to OFF.
  4. Set Outdoor Temp Sensor Exempt to YES only if the job really is exempt.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, Outdoor sensor exemption notice, p.2; Boiler Settings, p.58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.