Weil-McLain · Boiler troubleshooting

Check the flame signal

SVF 500/600 Series 1

What is going on

The control uses three flame signal thresholds: Boost, Shutdown and Proof of Flame.

Check in this order

  1. Press Home, then press and hold the WM logo until the Contractor menu appears.
  2. Press Diagnostics, then Manual Test Mode.
  3. With the boiler not in ignition or running, the flame signal should read 0.
  4. During ignition or running, a strong flame signal should read between 4 and 7.
  5. Check the flame signal at both high and low fire.
  6. Flame signal must stay above the thresholds in the flame signal table at all times; below Boost the control raises the firing rate to strengthen the flame.

Applies to: SVF 500/600 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 115. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.