Clean the condensate drain system, siphon and neutralizer
What is going on
Annual cleaning of the condensate drain system, which includes the flue collector, siphon, neutralizing system and hoses in between. Water must drain without back pressure.
Likely causes
- Debris or sediment in the condensate drain or siphon
- Neutralizer granulate used up or condensate pH below 6.5
Check in this order
- Check that the condensate drain and neutralizer are not blocked and do not leak.
- Add water to the combustion chamber and confirm it drains freely. Clean the drain again if there is back pressure.
- Undo fitting A on siphon B and remove the siphon from the boiler.
- Brush out inlet connector D.
- Remove bottom part C of the siphon, clean it and refit it.
- Fill the siphon with water before refitting it to inlet connector D. An unfilled siphon allows flue gas to escape.
- Clean inside the condensate drain system and the neutralizer (if installed).
- Measure condensate pH with a pH strip (field supplied). If pH is below 6.5, replace the granulate.
- If contaminated, rinse the neutralization unit with tap water.
- Add granulate up to the marked level.
- Disconnect the drain hose to the building drain from siphon B and reconnect the neutralizer to siphon B.
- Granulate is used up as it neutralizes the condensate. Check the neutralizer manual for minimum level.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.