Weil-McLain · Boiler troubleshooting
Add a DHW secondary connection for high-flow or high pressure-drop DHW
What is going on
Use this layout when DHW circuit flow exceeds what the boiler allows, or when a coil-type DHW tank has high pressure drop. DHW water flows only through the secondary connection piping.
Likely causes
- DHW flow rate above boiler limits
- High pressure-drop coil-type DHW tank
Check in this order
- Size the DHW secondary connector piping (Figure 17, item 23) for the full flow it must carry.
- Keep the DHW secondary connector tees no more than 8 pipe diameters apart.
- Install a system circulator sized for the required flow and head.
- Install a flow/check valve on the boiler outlet piping.
- Set DHW priority and space heating priority as shown in the priority setting table.
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.