Weil-McLain · Boiler troubleshooting

Add a DHW secondary connection for high-flow or high pressure-drop DHW

SlimFit Series 2

What is going on

Use this layout when DHW circuit flow exceeds what the boiler allows, or when a coil-type DHW tank has high pressure drop. DHW water flows only through the secondary connection piping.

Likely causes

  • DHW flow rate above boiler limits
  • High pressure-drop coil-type DHW tank

Check in this order

  1. Size the DHW secondary connector piping (Figure 17, item 23) for the full flow it must carry.
  2. Keep the DHW secondary connector tees no more than 8 pipe diameters apart.
  3. Install a system circulator sized for the required flow and head.
  4. Install a flow/check valve on the boiler outlet piping.
  5. Set DHW priority and space heating priority as shown in the priority setting table.

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.