Weil-McLain · Boiler troubleshooting

Burner flame and flame signal check

Ultra Series 4

What is going on

Check the flame and the flame signal reading in the U-Control.

Likely causes

  • Fouled or damaged ignitor if flame signal is low

Check in this order

  1. Look at the flame through the observation window (see p. 40) at high fire and low fire.
  2. If flame is unsatisfactory at either rate, shut off and let the boiler cool. Remove the burner and clean it with a vacuum or compressed air. Do not use compressed air indoors.
  3. To access the burner, remove the heat exchanger cover plate (p. 125).
  4. When reinstalling, check the burner gasket is in good condition and correctly positioned. Tighten the three retainer screws, then bend up the retainer tabs.
  5. Reattach the cover plate (see p. 126 or p. 127). Reinstall components and retest.
  6. Go to Diagnostics/Inputs on the U-Control and read the flame signal.
  7. Flame signal must be at least 20 above the shutdown value for the model (see flame signal table).
  8. If the signal is low, the U-Control raises firing rate to compensate. A low signal may mean a fouled or damaged ignitor. Clean it. If cleaning does not help and ground wiring and continuity are good, replace the ignitor.

Applies to: Ultra Series 4 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.