Viessmann · Boiler troubleshooting

Simplified leak test of coaxial vent (sealed combustion)

Vitodens 100-W, WB1B

What is going on

Applies only to sealed combustion with coaxial venting. Not applicable to single-wall venting.

Likely causes

  • Leak in the coaxial vent system

Check in this order

  1. Measure the CO2 concentration of the combustion air in the coaxial gap of the air intake pipe, using the air measurement port on the vent adaptor.
  2. Pass if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
  3. If CO2 is higher or O2 is lower, check the venting system thoroughly.

Applies to: Vitodens 100-W, WB1B, coaxial vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.