Expansion tank and make-up water sizing and piping
What is going on
An undersized expansion tank lets system water escape through the relief valve and pulls make-up water in through the fill valve. Excess make-up water eventually causes boiler failure.
Likely causes
- Expansion tank undersized for boiler and system volume
- Air vent operation on a closed-type tank system
Check in this order
- Size the expansion tank for the boiler and system volume and temperature. Allow 3 gallons for the boiler and its piping.
- Locate the tank as shown in the manual or by a recognized design method.
- Connect the tank to the air separator only if the separator is on the suction side of the circulator. Install the system fill connection at the same point as the tank connection.
- For a diaphragm or bladder tank, install an automatic air vent on top of the air separator. If the boiler is above the main piping, also install an automatic air vent in the top of the outgoing boiler piping.
- For a closed-type tank, do not install automatic air vents. Pitch horizontal piping up toward the tank 1 in. per 5 ft and connect to the tank with at least 3/4 in. pipe.
- Do not use a closed-type expansion tank with a Weil-McLain AQUA PLUS water heater. The water heater needs an automatic air vent, and the vent would waterlog a closed-type tank.
Applies to: All Ultra Series 4 models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.