Weil-McLain · Boiler troubleshooting
Wire external limit with manual reset
What is going on
Control locks out when this limit opens. A technician or operator must reset the control.
Likely causes
- External limit opened (for example high limit or other safety device)
Check in this order
- Remove the factory-installed jumper on J20 pins 1 and 2.
- Connect the isolated contacts of the external limits across J20 pins 1 and 2.
- If the limit opens, the control locks out, activates the alarm terminals, and shuts down the boiler.
- After the limit closes, reset the control manually using the procedure in this manual.
Applies to: ECO Tec Series 3 all models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 70. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.