Weil-McLain · Boiler troubleshooting

Wire external limit with manual reset

ECO Tec Series 3

What is going on

Control locks out when this limit opens. A technician or operator must reset the control.

Likely causes

  • External limit opened (for example high limit or other safety device)

Check in this order

  1. Remove the factory-installed jumper on J20 pins 1 and 2.
  2. Connect the isolated contacts of the external limits across J20 pins 1 and 2.
  3. If the limit opens, the control locks out, activates the alarm terminals, and shuts down the boiler.
  4. After the limit closes, reset the control manually using the procedure in this manual.

Applies to: ECO Tec Series 3 all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.