Wire a 240 VAC single-phase burner motor in conduit

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

For burners with a 240 VAC 1-phase supply run in conduit. Use the burner manual for fuse and wire size and the specific Viessmann connections.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect 240 VAC power to terminals 21, 22 and 23 on the DIN rail inside the connection enclosure.
  3. Provide a fuseable disconnect according to local codes.
  4. Connect the supplied power cable to the motor terminals on the burner.
  5. Connect the cable plug to the socket on the DIN rail in the connection enclosure.
  6. Use the factory-supplied cable and conduit.

Applies to: Burner motor, 240 VAC 1PH, VD2/VD2A/CT3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.