Weil-McLain · Boiler troubleshooting
Vertical direct vent: roof vent and air terminations
What is going on
Terminate vent and air through the roof or with a sidewall air inlet.
Check in this order
- Keep the total outside vent and air piping within the maximum lengths in the manual's termination figure (page 44).
- Use sweep elbows for all vent piping where possible.
- Slope vent piping at least 1/4 inch per foot toward the boiler.
- Support piping independently of the boiler every 5 feet, and within 6 inches of any upturn.
- Cut the air pipe hole to the vent/air pipe maker's size.
- Cut the vent pipe hole at least 3/8 in larger for combustible construction, or per the vent maker for noncombustible construction.
- Insert a corrosion-resistant metal thimble in the vent pipe hole and isolate the pipe per local codes.
- Use flashing and sealing boots sized for the vent pipe.
- Use a coupling or open-end termination per the vent maker's vertical termination guidelines.
- Install a bird screen in the open ends of the terminations.
- Keep the finished termination dimensions shown in the manual's figure.
- Seal all exterior openings with caulk.
Applies to: SVF 1500-3000 vertical direct vent (Category IV)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 43-44. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.