Viessmann · Boiler troubleshooting

Wire a combustion air damper

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Wire the combustion air damper to the boiler control through the combustion air device adaptor in the connection enclosure. Use the damper manual for the correct install. Confirm the damper is rated for this application.

Check in this order

  1. Disconnect power to the control and the burner.
  2. Wire the damper per the diagram adaptor in the connection enclosure, field-supplied 120 VAC relay coil, damper, end switch rated 120 VAC, and 120 VAC supply.
  3. Wire the end switch to the normally open terminal on the device adaptor board.
  4. Provide a disconnect and overcurrent protection as local codes require.
  5. Spring return dampers do not need the field-supplied relay.

Applies to: Combustion air damper wiring, single boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.