Removing the hydraulic unit (B1HE/KE 85/120)
What is going on
Removal sequence for the hydraulic unit on the 85 and 120 models.
Check in this order
- Remove the control unit.
- Unscrew the union nut at the top and the screws at the bottom of the gas pipe, holding the union nut with an open ended wrench.
- Remove the burner.
- Remove the clips, push the pipe upwards, pivot it backwards and remove it downwards.
- Pull the clip off the supply pipe and fit new cable ties when securing the clips.
- Pull off the clips and push the supply pipe upwards. Remove the safety valve with drain if necessary.
- Undo the screws at the bottom of the hydraulic unit.
- Unplug the cable.
- Raise the hydraulic unit and remove it toward the front.
- Refit in reverse order.
Applies to: B1HE and B1KE 85/120
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W B1HE/B1KE installation/service manual, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.