System layout 5: low-loss header with multiple mixing-valve circuits
What is going on
Multi-circuit layout with a low-loss header, several mixing-valve circuits and one circuit without a mixing valve, plus DHW. The manual states this layout requires assistance from a Viessmann sales representative.
Check in this order
- Contact the local Viessmann sales representative before designing this layout.
- Use a Vitotronic 200-H HK1B mixing valve control with LON module instead of the accessory kit and Vitocontrol if needed.
- Install the expansion tank in the location shown in the manual.
- Install the low-loss header and its Viessmann temperature sensor if required.
- Set the heating circuit pump 28/20 function per coding address 53.
Applies to: Vitocrossal 300 CU3A, system layout 5
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 48. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.