Set LON addresses for a Vitotronic 300 GW6B cascade
What is going on
The gateway expects the lead boiler at a fixed LON address. The default configuration is 8 GW6B boilers and 3 zones.
Check in this order
- Set the master or lead Vitotronic 300 GW6B to LON address 1 at coding address 77.
- Set the subsequent boilers to LON addresses 2 through 8.
- Keep the default configuration of 8 boilers and 3 zones unless the system differs.
Applies to: Vitotronic 300 GW6B used as master cascade control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.