Viessmann · Boiler troubleshooting

Set LON addresses for a Vitotronic 300 GW6B cascade

Versatronik 581 / 581D

What is going on

The gateway expects the lead boiler at a fixed LON address. The default configuration is 8 GW6B boilers and 3 zones.

Check in this order

  1. Set the master or lead Vitotronic 300 GW6B to LON address 1 at coding address 77.
  2. Set the subsequent boilers to LON addresses 2 through 8.
  3. Keep the default configuration of 8 boilers and 3 zones unless the system differs.

Applies to: Vitotronic 300 GW6B used as master cascade control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 581 LON gateway manual, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.