Do not common vent: removing an old boiler from a common vent
What is going on
The SVF cannot share a common vent with any other appliance, and it cannot use an existing common vent. Removing the old boiler can leave remaining appliances on an oversized vent, so the remaining appliances must be tested before the job is finished.
Likely causes
- Existing common vent is too large for the remaining appliances after the old boiler is removed
- Flue gas spillage or CO emissions when the remaining appliances vent poorly
Check in this order
- Inspect the existing vent for correct size, horizontal pitch, blockage, leakage, corrosion and other faults.
- Close building doors and windows, and doors to other spaces, as far as practical.
- Turn on clothes dryers and any appliance not on the common vent.
- Turn on exhaust fans such as range hoods and bathroom fans to full speed. Do not run a summer exhaust fan.
- Close fireplace dampers.
- Seal unused openings in the common vent.
- Run each remaining appliance alone, following its lighting instructions, with the thermostat set to call for continuous operation.
- After 5 minutes of main burner operation, check for spillage at the draft hood relief opening using a match, candle or smoke.
- Return doors, windows, fans, dampers and other gas appliances to their prior condition.
- Correct any improper common vent operation so it meets NFPA 54 or CAN/CSA B149.1. If resizing, approach the minimum size from NFPA 54 Chapter 13 or CAN/CSA B149.1.
Applies to: Replacement of a boiler on an existing common vent
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 Boiler Manual, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.