Gas piping pressure and leak test

Vitodens 200-W

What is going on

Tests above 14 in. w.c. (1/2 psig) require the boiler and its shutoff valve to be disconnected from the supply. At or below that level, isolate the boiler with its manual valve only.

Check in this order

  1. For tests at or below 1/2 psig (14 in. w.c.), keep the boiler isolated using its manual shutoff valve.
  2. For tests above 1/2 psig (14 in. w.c.), disconnect the boiler and its shutoff valve from the gas supply first.
  3. Perform a leak test with an approved liquid spray solution. Keep it off electrical parts, wires and connectors, and away from the gas valve regulator and regulator vent opening.
  4. Correct any leaks found and retest.
  5. Purge air from the gas line.
  6. Do not check for leaks with an open flame.

Applies to: Vitodens 200-W B2HB gas piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.