Gas piping pressure and leak test
What is going on
Tests above 14 in. w.c. (1/2 psig) require the boiler and its shutoff valve to be disconnected from the supply. At or below that level, isolate the boiler with its manual valve only.
Check in this order
- For tests at or below 1/2 psig (14 in. w.c.), keep the boiler isolated using its manual shutoff valve.
- For tests above 1/2 psig (14 in. w.c.), disconnect the boiler and its shutoff valve from the gas supply first.
- Perform a leak test with an approved liquid spray solution. Keep it off electrical parts, wires and connectors, and away from the gas valve regulator and regulator vent opening.
- Correct any leaks found and retest.
- Purge air from the gas line.
- Do not check for leaks with an open flame.
Applies to: Vitodens 200-W B2HB gas piping
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation manual, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.